micrologic 5e trip unit

Micrologic Trip Unit Power Supply

Internal Power Supply for Micrologic 5 and 6 Trip Units

The protection functions and the test functions of Micrologic 5 and 6 trip units operate with the current through the internal current transformers (CT).

When the load current is higher than 20% of the rated current In, the internal current supply provides the power supply for the full functioning of the Micrologic trip unit. This includes:

o The Micrologic display screen and LEDs

o The maintenance and diagnostic functions

To provide a power supply to the Micrologic 5 or 6 trip unit when the load is below 20% of the rated current In, and maintain the full functioning of the Micrologic trip unit, one of the following optional power supplies can be used:

o An external 24 Vdc power supply connected permanently to the Micrologic trip unit

o A power supply connected temporarily to the test port on the Micrologic trip unit:

o Pocket battery

o PC through USB maintenance interface

Each optional Micrologic power supply is described further.

Internal Power Supply for Micrologic 7 Trip Units with Integrated Earth-Leakage Protection

The protection functions and the test functions of Micrologic Vigi 7 trip units operate with the current through the internal current transformers (CT) and the internal voltage power supply. The Micrologic display screen, LEDs, and maintenance and protection functions are available whatever the load current.

External 24 Vdc Power Supply

The 24 Vdc power supply maintains the operation of the functions of the Micrologic trip unit in all circumstances, including in low load conditions (load below 20%), and when the circuit breaker is open and not energized.

The 24 Vdc power supply is essential to enable the Micrologic trip unit to display the trip cause.

The external 24 Vdc power supply is provided to the Micrologic trip unit once it is connected to another module in the ULP system (for example, IFM Modbus-SL interface for one circuit breaker).

When the Micrologic trip unit is not connected to a ULP module, it can be connected directly to an external 24 Vdc power supply by using the optional 24 Vdc supply terminal block.

One 24 Vdc power supply can be used to provide power to several Micrologic trip units or other ULP modules.

Recommended 24 Vdc Power Supplies

Available 24 Vdc power supplies include the range of Phaseo ABL8 power supplies and the AD power supplies. For more information, refer to the Masterpact MTZ Catalogue .

NOTE: For applications requiring an overvoltage category higher than II, install a surge arrester when using a 24 Vdc ABL8 power supply.

ULP Module Consumption

The following table lists the ULP module consumption:

For more information on power supplies, refer to ULP System (IEC Standard) - User Guide .

Pocket Battery

Check the charge level of the pocket battery by sliding the switch to the Test position. The green LED on the pocket battery lights up to indicate the battery status.

For more information on the pocket battery, refer to Compact NSX - Circuit Breakers and Switch-Disconnectors 100–630 A - User Guide .

USB Maintenance Interface

During periods of setting, commissioning, testing, and maintenance, the USB maintenance interface, connected to the test port on the Micrologic trip unit provides a temporary power supply.

For more information on the USB maintenance interface, refer to Compact NSX - Circuit Breakers and Switch-Disconnectors 100–630 A - User Guide .

DOCA0141EN-01

© 2020 Schneider Electric. All rights reserved.

  • Français - French
  • 中文 - Chinese (Simplified)
  • Español - Spanish (Castillian)
  • Cybersecurity Safety Notice
  • About the Book
  • Pact Series Master Range
  • ComPact NSX Range
  • Operating the Circuit Breaker
  • EcoStruxure Power Commission Software
  • De-Energizing the Circuit Breaker
  • Environmental Conditions
  • Front Face Description
  • Opening, Closing, and Resetting the Circuit Breaker
  • Testing the Circuit Breaker
  • Locking the Circuit Breaker
  • Testing a Circuit Breaker With Direct Rotary Handle
  • Locking a Circuit Breaker With Direct Rotary Handle
  • Testing a Circuit Breaker With Extended Rotary Handle
  • Locking a Circuit Breaker With Extended Rotary Handle
  • Opening, Closing, and Resetting a Circuit Breaker With Motor Mechanism
  • Opening, Closing, and Resetting Circuit Breakers With Communicating Motor Mechanism
  • Plug-in Circuit Breaker
  • Withdrawable Circuit Breaker
  • Accessories
  • Electrical Auxiliary Device Summary
  • Indication Contacts
  • Wireless Indication Auxiliary
  • SDTAM Module ( MicroLogic 2 M and 6 E-M )
  • 24 Vdc Power Supply Connector
  • BSCM Breaker Status Control Module
  • Insulated NSX Cord
  • Control Auxiliaries
  • PowerTag Energy M250/M630
  • Applications
  • Fault Currents in Electrical Distribution
  • Protection Against Overcurrents in Electrical Distribution
  • Protection Against Ground Faults
  • Protection for Motor-Feeders
  • Thermal-Magnetic Trip Unit Summary
  • TM-D Thermal-Magnetic Trip Unit for 1P and 2P Circuit Breakers
  • TM-D Thermal-Magnetic Trip Unit for 1P Circuit Breakers 250 A
  • TM-D Thermal-Magnetic Trip Unit for 3P and 4P Circuit Breakers up to 63 A
  • TM-D Thermal-Magnetic Trip Unit for 3P and 4P Circuit Breakers from 80 A to 250 A
  • TM-G Thermal-Magnetic Trip Unit
  • MA Magnetic Trip Unit
  • Earth-Leakage Protection by VigiPacT Add-on

Characteristics of MicroLogic Electronic Trip Units

  • MicroLogic 2 Electronic Trip Units
  • MicroLogic 4 Electronic Trip Units
  • MicroLogic 1.3 M Electronic Trip Unit
  • MicroLogic 2 M Electronic Trip Unit
  • MicroLogic 2 G Electronic Trip Unit
  • MicroLogic 2 AB and 4 AB Electronic Trip Units
  • MicroLogic Maintenance Interfaces
  • Pocket Battery
  • Service Interface Connected to a PC
  • Stand-Alone USB Maintenance Interface
  • USB Maintenance Interface Connected to a PC
  • Commissioning
  • Maintaining the Circuit Breaker During Operation
  • Responding to a Trip
  • Troubleshooting
  • ComPact NSX 100-250 - Distribution Protection Tripping Curves
  • ComPact NSX 100-250 - Motor-Feeder Protection Tripping Curves
  • ComPact NSX 400-630 - Distribution Protection Tripping Curves
  • ComPact NSX 400-630 - Motor-Feeder Protection Tripping Curves
  • ComPact NSX 100-630 - Reflex Tripping
  • ComPact NSX 100-630 - Limitation Curves

For the best experience of this site, please enable Javascript for the www.productinfo.schneider-electric.com domain.

Introduction

Protection of the electrical distribution or specific applications

Measurement of instantaneous values and measurement of average values (demand) for electrical quantities

Kilowatt hour metering

Operational assistance such as peak demand, customized alarms, and operation counters

Communication

Identification

Identify the trip unit installed on the circuit breaker by using the four characters on the front face:

micrologic 5e trip unit

MicroLogic Trip Unit Families

MicroLogic 1 , 2 , and 4 without display screen

MicroLogic 5 , 6 , and 7 with display screen.

By using the adjustment dials

By additional settings on the keypad. Setting values are displayed on the screen

Through EcoStruxure Power Commission software.

For more information about the MicroLogic 5 , 6 , and 7 trip units, refer to DOCA0141EN , ComPact NSX MicroLogic 5/6/7 Electronic Trip Units - User Guide .

In Rating of MicroLogic Trip Units

The In rating (in amps) of a MicroLogic trip unit corresponds to the maximum value of the long-time protection ( Ir ) setting range for the trip unit. The setting range is indicated on the label on the front face of the trip unit (this label is visible on the front face of the ComPact NSX circuit breaker after the trip unit has been fitted).

Setting range: 100-250 A

In rating = 250 A

Distribution Trip Unit

The following figure and table define the protection functions for distribution-type MicroLogic trip units.

Thermal Memory

The thermal memory is used to simulate temperature build-up and cooling in conductors caused by current variations, according to a time constant. In the event of an overload, the trip units with a thermal memory memorize the build-up temperature caused by the current. Memorizing the build-up temperature leads to a reduction in the trip time.

For MicroLogic 2 and 4 trip units, the time constant is 15 minutes.

For MicroLogic 5 , 6 , and 7 trip units, the time constant is 20 minutes.

Motor Trip Units

The following figure and table define the protection functions for MicroLogic type M trip units.

Motor Trip Unit: Additional Protection

MicroLogic type M trip units (in particular MicroLogic 6 E-M ) also incorporate additional protection for the motor application. For more information, refer to DOCA0141EN , ComPact NSX MicroLogic 5/6/7 Electronic Trip Units - User Guide ..

Indication LEDs

Indication LEDs on the front of the trip unit indicate its operational state.

The LEDs and their meaning depend on the type of MicroLogic trip unit.

Above 15 A on a MicroLogic trip unit rated 40 A

Above 30 A on MicroLogic trip units rated > 40 A

The limit value is indicated on the front panel, above the Ready LED of the MicroLogic trip unit. NOTE: For the MicroLogic 4 and 7 trip units, the protection functions are supplied by a second power supply, in addition to the current transformer supply. The Ready LED blinks irrespective of the load, indicating that the standard protection functions are operational.

Install a 24 Vdc external power supply module which allows the trip unit to be monitored continuously, even when the circuit breaker is open. For more information, refer to LVPED217032EN , ComPact NSX & NSXm Catalogue .

Or, during maintenance visits, connect the pocket battery to monitor the trip unit.

MicroLogic trip units feature a test port specifically for maintenance actions .

Use the test port to:

Connect a pocket battery for local testing of the MicroLogic trip unit

Connect the Service Interface for testing, setting the MicroLogic trip unit, updating the MicroLogic firmware, or for installation diagnostics with EcoStruxure Power Commission software

For push-to-trip test or installation diagnostics with the USB maintenance interface stand-alone

For testing and installation diagnostics, setting the MicroLogic trip unit, updating the MicroLogic firmware with the USB maintenance interface connected to a PC

Interchangeability of MicroLogic Trip Units

No connections to make

No specific tools (for example, calibrated torque wrench)

Compatibility of trip units provided by mechanical cap

Torque limited screw provides correct torque

The simplicity of the replacement process means that it is easy to make the necessary adjustments as operation and maintenance processes evolve. NOTE: The screw head is accessible when the trip unit is installed, so the trip unit can still be removed. NOTE: On ComPact NSX circuit breakers with NA , R , HB1 , HB2 , and K breaking performances the trip units are not interchangeable.

Sealing the Protection

Seal the transparent cover on MicroLogic trip units to prevent modification of the protection.

On MicroLogic 5 , 6 , and 7 trip units, it is possible to use the keypad, with the cover sealed, to read the protection settings and measurements.

Show QR code for this page

QR Code is a registered trademark of DENSO WAVE INCORPORATED in Japan and other countries.

Was this helpful?

Contact Information

Legal information.

The information provided in this document contains general descriptions, technical characteristics and/or recommendations related to products/solutions.

This document is not intended as a substitute for a detailed study or operational and site-specific development or schematic plan. It is not to be used for determining suitability or reliability of the products/solutions for specific user applications. It is the duty of any such user to perform or have any professional expert of its choice (integrator, specifier or the like) perform the appropriate and comprehensive risk analysis, evaluation and testing of the products/solutions with respect to the relevant specific application or use thereof.

The Schneider Electric brand and any trademarks of Schneider Electric SE and its subsidiaries referred to in this document are the property of Schneider Electric SE or its subsidiaries. All other brands may be trademarks of their respective owner.

This document and its content are protected under applicable copyright laws and provided for informative use only. No part of this document may be reproduced or transmitted in any form or by any means (electronic, mechanical, photocopying, recording, or otherwise), for any purpose, without the prior written permission of Schneider Electric.

Schneider Electric does not grant any right or license for commercial use of the document or its content, except for a non-exclusive and personal license to consult it on an "as is" basis.

Schneider Electric reserves the right to make changes or updates with respect to or in the content of this document or the format thereof, at any time without notice.

To the extent permitted by applicable law, no responsibility or liability is assumed by Schneider Electric and its subsidiaries for any errors or omissions in the informational content of this document, as well as any non-intended use or misuse of the content thereof.

© 2022 Schneider Electric

  • Get custom product tools and services
  • Access training
  • Manage support cases
  • Create and manage your orders (authorised partners only)

Welcome to the Schneider Electric Website

End of commercialization is the last date Schneider Electric will accept an offer for this reference. However, after Sales Services (repair, spare parts, etc.) will continue until its end of life.

Contact Customer Care Center - available 24 a day.

Schneider Electric LV429095 Picture

trip unit MicroLogic 5.2 E for ComPact NSX 100/160/250 circuit breakers, electronic, rating 100A, 3 poles 3d

Recommended replacement(s), lv429095 is replaced by:.

Schneider Electric C1035E100 Picture

Sustainability

REACh Declaration

Compliant with Exemptions

China RoHS declaration

Product out of China RoHS scope. Substance declaration for your information

micrologic 5e trip unit

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

IMAGES

  1. Square D S133A Micrologic 5.0 Trip Unit w/LSI Functions

    micrologic 5e trip unit

  2. Square D S133A Micrologic 5.0 Trip Unit w/LSI Functions

    micrologic 5e trip unit

  3. Electrical product information

    micrologic 5e trip unit

  4. Schneider M163A Micrologic 5.0 P Trip Unit w/LSI Functions

    micrologic 5e trip unit

  5. LV431491 Trip unit MicroLogic 5.2E for NSX250s

    micrologic 5e trip unit

  6. Range of Micrologic Trip Units

    micrologic 5e trip unit

VIDEO

  1. Micrologic 5.0 and 6.0 Tutorial for Schneider Circuit Breakers

  2. Testing Micrologic Trip Unit with Full Function Test Kit

  3. Replacing Micrologic Trip Unit on PowerPact™ P-Frame Breakers

  4. Viewing Peak Values on Micrologic Ammeter Trip Unit

  5. Configuring H, J or L Frame Micrologic Trip Units via Display

  6. Testing Reliability of Micrologic Trip Unit on NSX Circuit Breaker

COMMENTS

  1. Micrologic Trip Units

    Part of. PacT. Series. All Micrologic trip units provide impeccable, electronic circuit protection with adjustable protection settings for maximum system coordination and flexibility. Sophisticated functionality, such as energy and power quality metering capabilities, is integrated in the more advanced trip units.

  2. MicroLogic ™ Electronic Trip Systems

    The MicroLogic H trip unit provides additional sampling of the waveforms to measure and provide waveform capture of harmonic distortion to the 31st harmonic. MasterPact universal power circuit breakers use MicroLogic electronic trip systems to sense overcurrents and trip the circuit breaker. The MicroLogic basic trip unit is standard and all ...

  3. MicroLogic 5.0P and 6.0P Electronic Trip Units User Guide

    Find and download documentation for up to 100 products at once. Access to our Global Image Library.

  4. Description of the Micrologic 5 and 6 Trip Units

    Test Port. Micrologic trip units feature a test port specifically for maintenance actions. Use the test port to: o Connect a pocket battery for local testing of the Micrologic trip unit. o Connect the USB maintenance interface for testing, setting the Micrologic trip unit, and for installation diagnostics. For more information, refer to Compact NSX - Circuit Breakers and Switch-Disconnectors ...

  5. Range of Micrologic Trip Units

    Micrologic trip units are used on the Compact NSX circuit breakers. The range of Micrologic trip units consists of several families of electronic trip unit: o Micrologic 1, 2, trip units and Micrologic Vigi 4 trip units without display. o Micrologic 5, 6, trip units and Micrologic Vigi 7 trip units with display. A TM-D, TM-G, or MA trip unit.

  6. Setting MicroLogic 5.0 A/E Trip Unit

    Setting MicroLogic 2.0 A/E Trip Unit; Setting MicroLogic 5.0 A/E Trip Unit; Setting MicroLogic 6.0 A/E Trip Unit; Setting MicroLogic 7.0 A Trip Unit; Setting the Neutral Protection; Protection Functions of MicroLogic A/E Trip Unit. Long-Time Protection; Short-Time Protection; Instantaneous Protection; Ground-Fault Protection on MicroLogic 6.0 A ...

  7. Description of the MicroLogic 5 and 6 Trip Units

    Type of MicroLogic trip unit. Description. Distribution. Ready LED (green) blinks slowly when the standard protection functions of the electronic trip unit are operational. Overload pre-alarm LED (orange) lights when the load exceeds 90% of the Ir setting. Overload alarm LED (red) lights when the load exceeds 105% of the Ir setting. Motor.

  8. User manual, MicroLogic A and MicroLogic E control units, english

    Trip unit name MicroLogic 5.0 A MicroLogic 7.0 A MicroLogic 2.0 A MicroLogic 2.0 E MicroLogic 5.0 E MicroLogic 6.0 A Packing Units Unit Type of Package 1 PCE Number of Units in Package 1 1 Package 1 Height 0.300 cm Package 1 Width 21.000 cm Package 1 Length 30.000 cm Package 1 Weight 200.000 g Unit Type of Package 2 S02 Number of Units in ...

  9. PDF MicroLogic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units Unidades

    MicroLogic trip units can communicate with other devices if the optional Circuit Breaker Communication Module (BCM) is installed. For information on the register lists and other communication devices refer to bulletin 0613IB1313: Modbus Communications System. Trip Unit Settings.

  10. Characteristics control unit Micrologic 5.0, Masterpact NW Product data

    Packing Units Unit Type of Package 1 PCE Number of Units in Package 1 1 Package 1 Height 6.8 cm Package 1 Width 8.0 cm Package 1 Length 21.5 cm Package 1 Weight 365.0 g Offer Sustainability Sustainable offer status Green Premium product REACh Regulation REACh Declaration EU RoHS Directive Compliant with Exemptions Mercury free Yes China RoHS ...

  11. Characteristics of Micrologic Electronic Trip Units

    For more information about the Micrologic 5, 6, and 7 trip units, refer to DOCA0141EN, Compact NSX Micrologic 5/6/7 Electronic Trip Units - User Guide. In Rating of Micrologic Trip Units. The In rating (in amps) of a Micrologic trip unit corresponds to the maximum value of the long-time protection (Ir) setting range for the trip unit.

  12. External Power Supply

    Trip unit and communication module must use separate power supplies. Failure to follow these instructions can result in injury or equipment damage. The trip unit can be powered by: 24 Vdc external power supply (recommended). Over 150 V on the bottom circuit breaker terminals on two phases. Over 150 V on the top circuit breaker terminals with ...

  13. Trip unit MicroLogic 5.2E, ComPacT Product data sheet NSX100/160/250, 3

    Packing Units Unit Type of Package 1 PCE Number of Units in Package 1 1 Package 1 Height 9.5 cm Package 1 Width 11.0 cm Package 1 Length 15.0 cm Package 1 Weight 564.0 g Unit Type of Package 2 S03 Number of Units in Package 2 11 Package 2 Height 30.0 cm Package 2 Width 30.0 cm Package 2 Length 40.0 cm Package 2 Weight 6.646 kg Offer Sustainability

  14. Micrologic 5.0 E for MASTERPACT NT/NW fixed

    Micrologic 5.0 E for MASTERPACT NT/NW fixed. Local distributor code: 399352702. 47283. EAN Code: 3606480344763. Contact Sales Contact support Subscribe to the newsletter. arrow2_down. Sustainability. Green Premium TM label is Schneider Electric's commitment to delivering products with best-in-class environmental performance.

  15. PDF Micrologic™ 5.0H and 6.0H Electronic Trip Units

    MicroLogic 6.0H Trip Unit. The MicroLogic 6.0H trip unit provides selective and ground-fault protection for equipment ( 1200 A) (LSIG) and power measurement. A. Graphic display screen B. Protection menu button * C. Maintenance menu button* D. Metering menu button* E. Down button F. Up button G. Enter button H. Long-time pickup (Ir) switch

  16. Micrologic 5.0 E for MASTERPACT NW drawout

    Green Premium TM label is Schneider Electric's commitment to delivering products with best-in-class environmental performance. Green Premium promises compliance with the latest regulations, transparency on environmental impacts, as well as circular and low-CO 2 products. Guide to assessing product sustainability is a white paper that clarifies global eco-label standards and how to interpret ...

  17. Front face of a Micrologic Vigi 7 trip unit (Trip version):

    The Micrologic Vigi 7 electronic trip unit is available in two versions for earth-leakage detection: o The Trip version trips when earth-leakage is detected. o The Alarm version measures the earth-leakage current and indicates an earth-leakage fault on the display screen. When the SDx indication contact is present, it signals an earth-leakage ...

  18. Range of MicroLogic Trip Units

    Description of the MicroLogic 5, 6, and Vigi 7 Trip Units. MicroLogic 5, 6, and Vigi 7 trip units are available for electrical power distribution applications and motor protection applications:. In the electrical power distribution application, MicroLogic 5.2, 5.3, 6.2, 6.3, Vigi 7.2, and Vigi 7.3 trip units are designed to protect conductors, goods, and people in commercial and industrial ...

  19. Used SCHNEIDER ELECTRIC 33072 MICROLOGIC A DIGITAL CIRCUIT BREAKER TRIP

    Schneider Micrologic A Programmer Trip Unit, S143A, Merlin Gerin SPW Industrial. SCHNEIDER ELECTRIC 47602 MICROLOGIC DIGITAL CIRCUIT BREAKER TRIP UNIT . Business Industrial, Electrical Equipment Supplies, Circuit Breakers Disconnectors eBay! Related products. Asus Vivobook 16X 2023 Review: Versatile i5 Laptop with 100% sRGB Display and RTX2050 ...

  20. Micrologic Trip Unit Power Supply

    To provide a power supply to the Micrologic 5 or 6 trip unit when the load is below 20% of the rated current In, and maintain the full functioning of the Micrologic trip unit, one of the following optional power supplies can be used: o An external 24 Vdc power supply connected permanently to the Micrologic trip unit. o A power supply connected ...

  21. Characteristics of MicroLogic Electronic Trip Units

    MicroLogic electronic trip units provide the following functions: Protection of the electrical distribution or specific applications. Measurement of instantaneous values and measurement of average values (demand) for electrical quantities. Kilowatt hour metering. Operational assistance such as peak demand, customized alarms, and operation counters.

  22. MicroLogic 5.0P and 6.0P Electronic Trip Units User Guide

    This instruction bulletin provides information on display navigation, trip unit configuration, operation, and trip unit, rating plug, and battery... MicroLogic 5.0P and 6.0P Electronic Trip Units User Guide

  23. LV429095

    trip unit MicroLogic 5.2 E for ComPacT NSX 100/160/250 circuit breakers, electronic, rating 100A, 3 poles 3d. C1035E100. Important message: This product has been switched to new ComPacT range and is no longer commercialized. It will continue to be available in H1 2023 only limited to specific projects.