an electronic trip unit

Micrologic 4 Electronic Trip Units

Introduction

The Micrologic 4 electronic trip unit is designed to protect:

o Conductors in commercial and industrial electrical distribution.

o Goods and people in commercial and industrial electrical distribution.

On 4-pole circuit breakers, neutral protection is set on the Micrologic trip unit by using a three-position dial:

o 4P 3D: neutral unprotected

o 4P 3D + N/2: neutral protection at half the value of the phase pickup, 0.5 x Ir (not available on Micrologic trip unit with In ≤ 40 A)

o 4P 4D: neutral fully protected at Ir

The Micrologic 4 electronic trip unit is available in two versions for earth-leakage detection:

o The Trip version trips when earth-leakage is detected.

o The Alarm version measures the earth-leakage current and indicates an earth-leakage fault on the front face with the earth-leakage fault indicator, which changes from gray to yellow.

When the SDx indication contact is present, it signals an earth-leakage fault remotely.

Description

The adjustment dials and indications are on the front face.

The trip unit rating In corresponds to the maximum value of the setting range.

Setting the Long-Time Protection

The long-time protection pickup Ir is set by using two multi-position dials.

o The preset dial allows the pickup to be preset to the value Io (displayed in amperes on the dial).

The maximum preset value (maximum setting on preset dial) equals the trip unit rating value In.

o The adjustment dial can be used to fine-tune the pickup Ir (value displayed in multiples of Io on the dial).

The time delay tr for long-time protection cannot be adjusted.

The following table shows the value of the time delay tr for long-time protection (in seconds) according to the overload current (in multiples of Ir)

The precision range is -20%, +0%.

Setting the Short-Time Protection

The short-time protection pickup Isd is set by using a multi-position dial.

The setting value is expressed in multiples of Ir.

The precision range is +/- 15%.

The time delay tr for short-time protection cannot be adjusted:

o Non-trip time: 20 ms

o Maximum breaking time: 80 ms.

Setting the Instantaneous Protection

The pickup Ii for instantaneous protection cannot be adjusted.

The following table shows the value of the pickup Ii for instantaneous protection (in amperes) according to the trip unit rating In:

The time delay for instantaneous protection cannot be adjusted:

o Non-trip time: 0 ms

o Maximum breaking time: 50 ms.

Setting the Neutral Protection (4P Only)

The neutral selection dial gives a choice of three values for the neutral long-time and short-time protection pickups.

The following table shows the values of the pickup for neutral long-time protection (in multiples of Ir) and neutral short-time protection (in multiples of Isd) according to the dial position:

The time delay for the neutral long-time protection and short-time protection is the same as that for the phases.

Setting the Earth-Leakage Protection

The earth-leakage protection IΔn, type A, is set by using a multi-position dial.

The following table shows the value of the pickup IΔn for earth-leakage protection according to the trip unit rating In:

The OFF setting annuls any earth-leakage protection and the circuit breaker behaves as a standard circuit breaker for cable protection.

Setting the earth-leakage protection to OFF can be used to inhibit earth-leakage protection during periods of setting, commissioning, testing and maintenance.

Setting the Earth-Leakage Protection Time Delay

The time delay of the earth-leakage protection is set by using a multi-position dial.

When IΔn is set to 30 mA, the time delay Δt is always 0 ms regardless of the position of the dial (instantaneous tripping).

When IΔn is set above 30 mA, the time delay Δt can be adjusted to the following values:

o 0 ms

o 60 ms

o 150 ms

o 500 ms

o 1000 ms

Testing the Earth-Leakage Protection

The earth-leakage protection must be tested regularly by using the test button ( T ). Pressing the test button simulates a real leakage current passing through the toroid, and the earth-leakage fault indicator displays the following symbol:

When the earth-leakage protection pickup IΔn is set to the OFF  position, pressing the test button has no effect.

In the case of the Trip version of Micrologic 4, pressing the test button trips the circuit breaker.

In the case of the Alarm version of Micrologic 4, pressing the test button causes the earth-leakage indicator to change to yellow.

If the circuit breaker does not trip, or the earth-leakage indicator does not change to yellow, check that the circuit breaker is energized. If the circuit breaker is energized correctly, and has not tripped or indicated the earth-leakage fault, replace the Micrologic 4 trip unit.

Resetting the Circuit Breaker After an Earth-leakage Fault Trip

Resetting the circuit breaker after an earth-leakage fault trip depends on the version:

o For the Trip version, reset the circuit breaker by moving the handle from Trip  to O (OFF)  position, and then to I (ON) position.

o For the Alarm version, press the test button ( T ) for three seconds.

For Trip and Alarm versions, the earth-leakage fault indicator changes back to gray after the reset.

Examples of Setting the Long-Time Protection

Example 1: Setting the long-time protection pickup Ir to 140 A on a Micrologic 4.2 trip unit rated In 250 A:

Example 2: Setting the long-time protection pickup Ir to 133 A on a Micrologic 4.2 trip unit rated In 250 A:

The actions in steps (2) and (3) on the adjustment dials modify the trip curves as shown:

Example of Setting the Short-Time Protection

Setting the short-time protection pickup Isd to 400 A on a Micrologic 4.2 rated In 250 A on a 133 A feed:

The action in step (2) on the adjustment dial modifies the trip curve as shown:

Example of Setting the Earth-Leakage Protection

Setting the earth-leakage protection pickup IΔn to 1 A with a tripping time delay of 500 ms on a Micrologic 4.2 rated In 250 A:

DOCA0140EN-01

© 2020 Schneider Electric. All rights reserved.

  • Français - French
  • 中文 - Chinese (Simplified)
  • Español - Spanish (Castillian)
  • Cybersecurity Safety Notice
  • About the Book
  • Pact Series Master Range
  • ComPact NSX Range
  • Operating the Circuit Breaker
  • EcoStruxure Power Commission Software
  • De-Energizing the Circuit Breaker
  • Environmental Conditions
  • Front Face Description
  • Opening, Closing, and Resetting the Circuit Breaker
  • Testing the Circuit Breaker
  • Locking the Circuit Breaker
  • Testing a Circuit Breaker With Direct Rotary Handle
  • Locking a Circuit Breaker With Direct Rotary Handle
  • Testing a Circuit Breaker With Extended Rotary Handle
  • Locking a Circuit Breaker With Extended Rotary Handle
  • Opening, Closing, and Resetting a Circuit Breaker With Motor Mechanism
  • Opening, Closing, and Resetting Circuit Breakers With Communicating Motor Mechanism
  • Plug-in Circuit Breaker
  • Withdrawable Circuit Breaker
  • Accessories
  • Electrical Auxiliary Device Summary
  • Indication Contacts
  • Wireless Indication Auxiliary
  • SDTAM Module ( MicroLogic 2 M and 6 E-M )
  • 24 Vdc Power Supply Connector
  • BSCM Breaker Status Control Module
  • Insulated NSX Cord
  • Control Auxiliaries
  • PowerTag Energy M250/M630
  • Applications
  • Fault Currents in Electrical Distribution
  • Protection Against Overcurrents in Electrical Distribution
  • Protection Against Ground Faults
  • Protection for Motor-Feeders
  • Thermal-Magnetic Trip Unit Summary
  • TM-D Thermal-Magnetic Trip Unit for 1P and 2P Circuit Breakers
  • TM-D Thermal-Magnetic Trip Unit for 1P Circuit Breakers 250 A
  • TM-D Thermal-Magnetic Trip Unit for 3P and 4P Circuit Breakers up to 63 A
  • TM-D Thermal-Magnetic Trip Unit for 3P and 4P Circuit Breakers from 80 A to 250 A
  • TM-G Thermal-Magnetic Trip Unit
  • MA Magnetic Trip Unit
  • Earth-Leakage Protection by VigiPacT Add-on

Characteristics of MicroLogic Electronic Trip Units

  • MicroLogic 2 Electronic Trip Units
  • MicroLogic 4 Electronic Trip Units
  • MicroLogic 1.3 M Electronic Trip Unit
  • MicroLogic 2 M Electronic Trip Unit
  • MicroLogic 2 G Electronic Trip Unit
  • MicroLogic 2 AB and 4 AB Electronic Trip Units
  • MicroLogic Maintenance Interfaces
  • Pocket Battery
  • Service Interface Connected to a PC
  • Stand-Alone USB Maintenance Interface
  • USB Maintenance Interface Connected to a PC
  • Commissioning
  • Maintaining the Circuit Breaker During Operation
  • Responding to a Trip
  • Troubleshooting
  • ComPact NSX 100-250 - Distribution Protection Tripping Curves
  • ComPact NSX 100-250 - Motor-Feeder Protection Tripping Curves
  • ComPact NSX 400-630 - Distribution Protection Tripping Curves
  • ComPact NSX 400-630 - Motor-Feeder Protection Tripping Curves
  • ComPact NSX 100-630 - Reflex Tripping
  • ComPact NSX 100-630 - Limitation Curves

For the best experience of this site, please enable Javascript for the www.productinfo.schneider-electric.com domain.

Introduction

Protection of the electrical distribution or specific applications

Measurement of instantaneous values and measurement of average values (demand) for electrical quantities

Kilowatt hour metering

Operational assistance such as peak demand, customized alarms, and operation counters

Communication

Identification

Identify the trip unit installed on the circuit breaker by using the four characters on the front face:

an electronic trip unit

MicroLogic Trip Unit Families

MicroLogic 1 , 2 , and 4 without display screen

MicroLogic 5 , 6 , and 7 with display screen.

By using the adjustment dials

By additional settings on the keypad. Setting values are displayed on the screen

Through EcoStruxure Power Commission software.

For more information about the MicroLogic 5 , 6 , and 7 trip units, refer to DOCA0141EN , ComPact NSX MicroLogic 5/6/7 Electronic Trip Units - User Guide .

In Rating of MicroLogic Trip Units

The In rating (in amps) of a MicroLogic trip unit corresponds to the maximum value of the long-time protection ( Ir ) setting range for the trip unit. The setting range is indicated on the label on the front face of the trip unit (this label is visible on the front face of the ComPact NSX circuit breaker after the trip unit has been fitted).

Setting range: 100-250 A

In rating = 250 A

Distribution Trip Unit

The following figure and table define the protection functions for distribution-type MicroLogic trip units.

Thermal Memory

The thermal memory is used to simulate temperature build-up and cooling in conductors caused by current variations, according to a time constant. In the event of an overload, the trip units with a thermal memory memorize the build-up temperature caused by the current. Memorizing the build-up temperature leads to a reduction in the trip time.

For MicroLogic 2 and 4 trip units, the time constant is 15 minutes.

For MicroLogic 5 , 6 , and 7 trip units, the time constant is 20 minutes.

Motor Trip Units

The following figure and table define the protection functions for MicroLogic type M trip units.

Motor Trip Unit: Additional Protection

MicroLogic type M trip units (in particular MicroLogic 6 E-M ) also incorporate additional protection for the motor application. For more information, refer to DOCA0141EN , ComPact NSX MicroLogic 5/6/7 Electronic Trip Units - User Guide ..

Indication LEDs

Indication LEDs on the front of the trip unit indicate its operational state.

The LEDs and their meaning depend on the type of MicroLogic trip unit.

Above 15 A on a MicroLogic trip unit rated 40 A

Above 30 A on MicroLogic trip units rated > 40 A

The limit value is indicated on the front panel, above the Ready LED of the MicroLogic trip unit. NOTE: For the MicroLogic 4 and 7 trip units, the protection functions are supplied by a second power supply, in addition to the current transformer supply. The Ready LED blinks irrespective of the load, indicating that the standard protection functions are operational.

Install a 24 Vdc external power supply module which allows the trip unit to be monitored continuously, even when the circuit breaker is open. For more information, refer to LVPED217032EN , ComPact NSX & NSXm Catalogue .

Or, during maintenance visits, connect the pocket battery to monitor the trip unit.

MicroLogic trip units feature a test port specifically for maintenance actions .

Use the test port to:

Connect a pocket battery for local testing of the MicroLogic trip unit

Connect the Service Interface for testing, setting the MicroLogic trip unit, updating the MicroLogic firmware, or for installation diagnostics with EcoStruxure Power Commission software

For push-to-trip test or installation diagnostics with the USB maintenance interface stand-alone

For testing and installation diagnostics, setting the MicroLogic trip unit, updating the MicroLogic firmware with the USB maintenance interface connected to a PC

Interchangeability of MicroLogic Trip Units

No connections to make

No specific tools (for example, calibrated torque wrench)

Compatibility of trip units provided by mechanical cap

Torque limited screw provides correct torque

The simplicity of the replacement process means that it is easy to make the necessary adjustments as operation and maintenance processes evolve. NOTE: The screw head is accessible when the trip unit is installed, so the trip unit can still be removed. NOTE: On ComPact NSX circuit breakers with NA , R , HB1 , HB2 , and K breaking performances the trip units are not interchangeable.

Sealing the Protection

Seal the transparent cover on MicroLogic trip units to prevent modification of the protection.

On MicroLogic 5 , 6 , and 7 trip units, it is possible to use the keypad, with the cover sealed, to read the protection settings and measurements.

Show QR code for this page

QR Code is a registered trademark of DENSO WAVE INCORPORATED in Japan and other countries.

Was this helpful?

Contact Information

Legal information.

The information provided in this document contains general descriptions, technical characteristics and/or recommendations related to products/solutions.

This document is not intended as a substitute for a detailed study or operational and site-specific development or schematic plan. It is not to be used for determining suitability or reliability of the products/solutions for specific user applications. It is the duty of any such user to perform or have any professional expert of its choice (integrator, specifier or the like) perform the appropriate and comprehensive risk analysis, evaluation and testing of the products/solutions with respect to the relevant specific application or use thereof.

The Schneider Electric brand and any trademarks of Schneider Electric SE and its subsidiaries referred to in this document are the property of Schneider Electric SE or its subsidiaries. All other brands may be trademarks of their respective owner.

This document and its content are protected under applicable copyright laws and provided for informative use only. No part of this document may be reproduced or transmitted in any form or by any means (electronic, mechanical, photocopying, recording, or otherwise), for any purpose, without the prior written permission of Schneider Electric.

Schneider Electric does not grant any right or license for commercial use of the document or its content, except for a non-exclusive and personal license to consult it on an "as is" basis.

Schneider Electric reserves the right to make changes or updates with respect to or in the content of this document or the format thereof, at any time without notice.

To the extent permitted by applicable law, no responsibility or liability is assumed by Schneider Electric and its subsidiaries for any errors or omissions in the informational content of this document, as well as any non-intended use or misuse of the content thereof.

© 2022 Schneider Electric

Electronic Trip Circuit Breaker Basics: Schneider Electric Micrologic Trip Units

What is electronic trip circuit breakers .

An electronic trip circuit breaker is a type of circuit breaker that uses electronic components to control the tripping mechanism instead of traditional thermal-magnetic trip elements. Electronic trip circuit breakers are commonly used in industrial and commercial applications where high reliability and selective coordination are required.

These circuit breakers use a solid-state trip unit to sense and respond to overcurrent conditions. The trip unit monitors the current flowing through the circuit breaker and can be programmed to trip at specific current levels and time delays. This allows for greater precision in protecting against overcurrent conditions and reduces the risk of nuisance trips. Electronic trip circuit breakers can also provide advanced monitoring and diagnostic capabilities. Some models can provide real-time current and voltage measurements, as well as fault event recording and reporting. This information can be used to identify potential issues and optimize system performance.

Related Article:  Circuit Breaker Essentials 

Why Use Electronic Trip Circuit Breakers? 

In most cases, the basic overcurrent protection provided by standard thermal-magnetic circuit breakers will meet the requirements of the electrical system design. In some cases, however, basic overcurrent protection might not be enough. Electronic trip circuit breakers can provide the additional features needed in those cases.

Reasons to use electronic trip circuit breakers includes:

  • Enhanced coordination capabilities
  • Integral ground-fault detection
  • Communication capabilities
  • Future growth potential

Enhanced Coordination Capabilities

Schneider electric micrologic electronic trip units.

  • Independent adjustments  - allow one dial setting to be changed without affecting the rest of the pickup and delay levels. This allows the designer to better define the tripping characteristics needed on the system. 
  • Interchangeable rating plugs-  allow the designer to shift the entire trip characteristic curve (except for ground fault) to improve coordination with other devices. MICROLOGIC rating plugs define the circuit breaker's maximum current rating based on a percentage of the circuit breaker sensor size and can be used on any frame size of circuit breaker within the MICROLOGIC family of circuit breakers. 
  • Withstand ratings give the designer a larger window of coordination potential - The withstand rating is the level of rms symmetrical current that a circuit breaker can carry with the contacts in the closed position for a certain period of time. At current levels above the withstand rating (and less than or equal to the interrupting rating), the circuit breaker will trip instantaneously. In other words, the withstand rating is the highest current level at which delay can be introduced to maintain coordination with downstream devices. Withstand ratings are available only on full-function trip systems ordered with the adjustable short-time function.
  • Inverse time delay characteristics  - allow for better coordination with fusible switches or thermal-magnetic circuit breakers downstream. Devices that respond to heat generated by current flow (such as fuses and thermal-magnetic circuit breakers) have inverse time tripping characteristics. This means that as current increases, the time that it takes the device to trip will decrease. In order to coordinate better with these types of downstream devices, MICROLOGIC circuit breakers offer inverse time delay characteristics on the long-time, short time and ground-fault functions. 
  • Ammeter/trip indicator - displays the level of ground-fault leakage current associated with the circuit. The ground-fault pickup level on the circuit breaker may then be adjusted somewhat higher than the amount of leakage current displayed on the ammeter.

Integral Ground Fault Protection

Communication capabilities.

  • History of last trip
  • Trip unit pickup and delay levels
  • Impending trip conditions
  • Operating currents for each phase
  • Ground-fault leakage current associated with the circuit
  • Ground-fault alarm signal

Standard Function Trip Unit Curves

Long term trip function.

  • LONG-TIME PICKUP Switch — switch value (multiplied by the ampere rating) sets the maximum current level which the circuit breaker will carry continuously. If the current exceeds this value for longer than the set delay time, the circuit breaker will trip. 
  • LONG-TIME DELAY Switch — sets length of time that the circuit breaker will carry a sustained overload before tripping. Delay bands are labeled in seconds of overcurrent at six times the ampere rating. For maximum coordination, eight delay bands are available.

Short-time Trip Function

  • SHORT-TIME PICKUP Switch — switch value (multiplied by the ampere rating) sets the short-circuit current level at which the circuit breaker will trip after the set SHORT-TIME DELAY.
  • SHORT-TIME DELAY Switch — sets length of time the circuit breaker will carry a short circuit within the short-time pickup range. Delay bands are labeled in seconds of short-circuit current at 12 times the ampere rating, P. The short-time delay can be set to one of four I^2t ramp operation positions (I^2t IN).

Instantaneous Trip Function

  • INSTANTANEOUS PICKUP Switch — switch value (multiplied by the ampere rating) sets the short-circuit current level at which the circuit breaker will trip with no intentional time delay. The instantaneous function will override the short-time function if the INSTANTANEOUS PICKUP is adjusted at the same or lower setting than the SHORT-TIME PICKUP. 
  • GROUND-FAULT PICKUP Switch — switch value (multiplied by the sensor size) sets the current level at which the circuit breaker will trip after the set GROUND-FAULT DELAY.
  • GROUND-FAULT DELAY Switch — sets the length of time the circuit breaker will carry ground-fault current which exceeds the GROUND-FAULT PICKUP level before tripping. Delay bands are labeled in seconds of ground-fault current at 1 times the sensor size, S. Ground-fault delay can be adjusted to one of four fixed time delay positions (I^2t OUT). 

In Comparison with Thermal Magnetic Circuit Breakers

View or download pdf.

Electronic Trip Circuit Breaker Basics: Schneider Electric Micrologic Trip Units

You Might Also Like

No comments:, follow us on facebook.

Latest Post

Green electronics: sustainable pcb manufacturing practices.

Image

Popular Topics

Voltage drop calculation based on national electrical code.

Image

How To Prepare Schedule of Loads

Image

How to Calculate Voltage Drop of Distributed Loads

Image

What is SELV and PELV Circuits?

Image

How to Calculate Transformer Voltage Drop

Image

What is the Importance of X/R Ratio?

Image

How to Perform Coordination Study of OCPD and Cable in Electrical Design

Image

What is Multiple Earthed Neutral?

Image

Types and Classes of Current Transformers According to IEC 60441

Image

How to conduct polarity testing?

Spectra RMS* Electronic Trip -Previous Generation Circuit Breakers

an electronic trip unit

Need help migrating from Spectra to Tmax XT?

Spectra breakers are now in the Limited life cycle phase. For circuit breakers, see SACE® Tmax® XT MCCBs . For retrofits of existing equipment, see Tmax XT Retrofit Kits for Spectra Panelboards and Switchboards .

Spectra RMS* Electronic Trip migration image

Related Videos

an electronic trip unit

Related Products

an electronic trip unit

Publications

  • Application and Technical
  • Installation and Instruction
  • Time Current Curves

Other Previous Generation Circuit Breakers

  • Get custom product tools and services
  • Access training
  • Manage support cases
  • Create and manage your orders (authorized partners only)

Welcome to the Schneider Electric Website

Search FAQs

What are thermal-magnetic or electronic trip unit, released for: schneider electric thailand.

Articles that might be helpful

Discuss this topic with experts

Start here!

Find answers now. Search for a solution on your own, or connect with one of our experts.

Contact Support

Reach out to our customer care team to receive more information, technical support, assistance with complaints and more.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Search topic-related frequently asked questions to find answers you need.

Contact Sales

Start your sales inquiry online and an expert will connect with you.

an electronic trip unit

Uncategorized

Evolution of the molded case circuit breaker trip units and their value to customers.

an electronic trip unit

Even though an 1879 patent filed by Thomas Edison provided a glimpse of the definition of what would become circuit breakers, fuses (use once and throw away) were the standard for the first 30-40 years in power distribution systems.1 In 1924, German inventor Hugo Stotz created and patented what was marketed as a re-settable fuse (Figure 1). It was a direct retrofit into common fuse panels of the day. The Stotz fuse incorporated a thermal element to detect and open contacts to clear overloaded or shorted circuits.2 This was a forerunner of the thermal-magnetic breaker (Figure 2) widely used in today’s power distribution systems.

How have circuit breakers evolved since the Stotz? More importantly, how can you take advantage of new circuit breaker technology to deliver to your clients a better tailored and user-friendly project? This brief article will focus specifically on the evolution of the breaker trip unit and the value this evolution provides to customers.

Circuit Breaker and Trip Unit

In order to understand what a trip unit is, let’s revisit the definition of a circuit breaker. A circuit breaker is a mechanical switching device designed to automatically detect and eliminate short circuits and overload current. A trip unit, specifically, is the “brain” of the circuit breaker as its function is to measure physical parameters such as electrical current and decide when to “trip” or rapidly open the mechanical contacts of the circuit breaker. At the bare minimum, a trip unit needs to offer overload and short circuit protection. In regard to the topic of evolution, the trip unit can be as simple as a bi-metallic strip, or now, as advanced as a computer. This evolution has opened the door to so much more than overload and short circuit protection – it’s opened a whole new world of protection, measurement, and control.

Let’s take a look at the evolution of the circuit breaker trip unit in four stages, starting with the basic thermal magnetic circuit trip unit, which is still the most widely used trip mechanism today.

Thermal Magnetic Circuit Trip Unit

The basic thermal magnetic circuit trip unit still provides a cost-effective solution for basic circuit protection and remains in widespread use. With the growth of critical electrical loads, the need for accurate and coordinated circuit protection has become much more important. However, the lower accuracy sensitivity offered by a thermal magnetic breaker cannot fully address this increasing demand. These shortcomings are amplified when you need breakers to trip in a coordinated fashion where only the problematic circuit is taken out of service. This is called selectivity and was a primary driver in the evolution from the thermal magnetic trip unit to the electronic trip unit which can provide a much higher degree of accuracy in sensing and responding to trip events.

Figure 3 exemplifies the typical response of a thermal magnetic breaker in the form of a time current curve (TCC). The X axis represents current and Y axis represents time, in seconds. The grid is logarithmic on both the X and Y axis. The breaker has two elements – ‘L’ or long time for the thermal, and ‘I’ for the magnetic. Note the width of the long-time element indicates a substantial lack of accuracy. Also note that the breaker’s response is significantly affected by temperature. There are two long time curve sections shown. The blue section is the ‘cold’ response and the orange section is the ‘hot’ response. The lack of accuracy makes coordination between thermal magnetic breakers difficult.

First Generation Electronic Trip Units

As noted earlier, this lack of accuracy, along with the growing need for coordinated circuit protection, drove the development of the electronic trip unit. First generation electronic trip units (Figure 4) were simple analog circuits comprised of resistors, capacitors, inductors, and transistors, however, they offered increased accuracy over their thermal magnetic cousins. Electronic trip breakers could be reasonably coordinated and be used to build a selectively coordinated distribution system.

Over the years, electronic trip units underwent incremental improvements including:

  • Limited Adjustability – Provided ability to make basic adjustments to instantaneous and overload response to improve selectivity
  • True RMS Sensing – Improved accuracy, bringing measurement much closer to the thermal response (not just looking at peak) of the current
  • Thermal Memory – Ensured (even lacking the inherent “heater” present in original thermal magnetic breakers) that trip data could be retained and remembered for reporting
  • Overall Improvement in Equipment Protection – Due to these enhancements which allowed more selectivity and eliminated the nuisance of premature trips which can damage the equipment

Modern Microprocessor Trip Units

As these electronic trip units continued to evolve, manufacturers used more and more sophisticated and integrated circuits which slowly evolved trip units into the modern microprocessor trip unit. The microprocessor trip unit provides even more improved protection accuracy and adjustability (ability to coordinate breakers closer together thus allowing additional breakers to operate in series IE levels of protection). Electronic trip unit breakers are commonly referred to as ‘LSI’ or ‘LSIG’ where ‘L’ is the long-time trip (60-600 sec), ‘S’ is the short time trip (0.1 to 60 sec), and ‘I’ is the instantaneous trip. ‘G’ is the optional ground fault trip. The ‘L’ and ‘S’ functions replace the thermal element in the thermal magnetic circuit breaker and the ‘I’ replaces the magnetic element. Figures 5 and 6 show the difference in response and adjustability between thermal magnetic and LSIG circuit breakers.

Figure 7 shows the time current curve of a typical breaker with a microprocessor LSI trip unit. Note the increased accuracy and adjustability in comparison with the thermal magnetic breaker.

This improved accuracy and adjustability of LSI breakers allowed for more advanced coordination of increasing layers of panels/circuit breakers in series.

Application Example

A building with a 2000A main switchboard and multiple power panels scattered throughout. Thermal magnetic breakers may allow up to three levels of coordination – switchboard main to switchboard feeder to power panel branch. Suppose the power panels were then feeding lighting panels. The lighting panel branch circuits can not be coordinated as it is the fourth level of coordination. If LSI breakers were used, the same system could be coordinated through the lighting panel and possibly with an additional panel in between (5 levels).

These evolving microprocessor trip units also provide much improved coordination with different types of protective devices such as motor starters, fuses, and relays, as well as the key ZSI (Zone Selective Interlocking) ability which allows planned overlap to gain maximum protection.

One big weakness that had yet to evolve was the advancement of sensors. So, while these electronic microprocessor trip units along with the right add-on equipment could provide early versions of metering from the circuit itself, the data was very inaccurate.

Today’s Advanced Next Generation Microprocessor Trip Units

Finally, we come to today’s advanced microprocessor trip units which are still microprocessor based, but because of the continued miniaturization in electronics to provide additional power, memory, and storage, and with a big change in sensor technology, these new breakers are a quantum leap ahead of their predecessors.

With the evolution of breaker trip units starting with basic overcurrent protection, you now have advanced capabilities that offer a host of additional protective functions nearly equal to functions offered by medium/high voltage multi-function relays. A few key features to look for include monitoring capabilities such as voltage, power quality, and even temperature of external sensors connected to the breaker.

Much of the new functionality is made possible by the replacement of the lower accuracy non-linear iron core current transformers with highly accurate linear current sensors. These sensors are based on the Rogowski coil concept. With traditional iron core current transformers, there is a tradeoff between measurement range and accuracy. Circuit breakers require sensing a large range of currents and accuracy is not as important. Today’s demands for metering require a smaller sensing range and much greater accuracy. The Rogowski coil sensor can cover a wide range of currents and has a very linear response. It is the perfect sensor for both protection and metering.

As mentioned, the real leap in value is moving so many functions “on board” the breaker trip unit that, in the past, could only be delivered by purchasing, integrating, and programming separate devices. A few examples (many more to explore) include:

  • Built in programmable logic – Moves functions formerly available only through the addition of one or more PLCs, such as automatic source transfer, load shedding, load control, and generator control
  • Communications – Standard network connections, additional communications technology such as IEC6185/GOOSE to high-speed breaker to breaker communications and coordination, including serving as a bridge between LV/MV applications.
  • Metering – Ability to delivery revenue-class metering (typically 1% accuracy), harmonic measurement and reporting, and power quality monitoring
  • Commissioning – Allows direct access to trip units via HMI panel (one panel for multiple breakers), or USB device (just copy over the settings), or even Bluetooth connection (outside the arc-flash zone)

The Evolution Will Certainly Continue

We’ve touched on the evolution of the circuit breaker trip unit across a century. Generally, three key technical advancements have opened up the possibilities of today’s advanced circuit protection with a molded case breaker – increased processor power (intelligence) due to advances in circuit board/component miniaturization, increased sensor accuracy as advances allowed for the application of the Rogowski coil for linear measurement, and the continued improvements to high-speed communications both in the processor capabilities and communication protocols. Overall, these three things combine to deliver the key cornerstone values required in smarter, safer, and more reliable power – accuracy plus the ability to make decisions and execute responses in milliseconds.

These capabilities will continue to evolve, and you and your customers will continue to benefit from the advancement of cheaper and more available raw computing power and communications over time.

  • Friedel, R., & Israel, P. (1987). Edison’s electric light biography of an invention. New Brunswick, NJ, NJ: Rutgers Univ. Pr.
  • Riemensperger, S. (2014, October 31). Miniature Breakers Stop Overloads, Short Circuits. Retrieved July 22, 2020, from com/conversations
  • Electrical installation handbook – Protection, control and electrical devices (Sixth ed., ABB Technical Guide). (2010). Bergamo Italy: ABB SACE.
  • Figure 3 – 3. (n.d.). In A Working Manual on Molded Case Circuit Breakers (Third ed.). Beaver, PA: Westinghouse Electric Corporation

Leave a Reply Cancel reply

Your email address will not be published. Required fields are marked *

Save my name, email, and website in this browser for the next time I comment.

SACE Tmax T

A complete range of moulded case circuit-breakers up to 3200 a..

All the circuit-breakers, both three-pole and four-pole, are available in the fixed version; sizes T4 and T5 in the plug-in version and T4, T5, T6, and T7 also in the withdrawable one.

High breaking capacity in compact dimensions High values of short circuit breaking capacity are guaranteed at different voltage levels, without compromising overall dimensions.

Flexibility of use Thermomagnetic and electronic trip units are available for use in AC/DC or in AC only. It is possible to interchange trip units keeping the same breaking part, so that installation can be upgraded with fewer costs.

Advanced protection A complete range of electronic trip units is suitable for different level of protection, even enhancing selectivity values with Early Fault Detection and Prevention algorithm.

an electronic trip unit

Are you looking for support or purchase information?

an electronic trip unit

ABB helps Te Papa ensure safe power supply

New Zealand’s national museum Te Papa, located in Wellington, is using SACE Tmax T Molded Case Circuit-Breakers to ensure reliable power and protection

an electronic trip unit

Plain sailing with specialized ABB smart circuit breakers

In a bid to provide critically important electrical systems for ships, ORTEC turned to ABB’s space-saving breakers, built with the highest resistance to shock, temperature and humidity

an electronic trip unit

ABB launches molded case circuit breakers for higher voltage solar power plants

ABB completes the offer for a single-brand solution up to 1500V DC and 800V AC

an electronic trip unit

Extended Warranty Tool for Active Circuit Breakers

To extend the warranty of ABB Low Voltage Circuit Breakers, ABB extends the warranty to customers in addition to the standard warranty by: +1 year (free of charge) and/or +3 years  on • new equipment  • purchased products (within factory standard warranty time=12months)  

an electronic trip unit

ABB plays a principal role in staging modernization of Basel Theater

To meet the demanding needs of the theater project, ABB provided its highly flexible System pro E power distribution switchboard.

an electronic trip unit

IE3-ready low voltage products. We are ready. Are you?

ABB control and protection low voltage products are IE3 ready. Our motor control solutions for high-efficiency motors can save you significant panel space. Learn more!

an electronic trip unit

ABB launches first low voltage moulded-case hybrid switch

Increasing efficiency and lowering costs for emerging technology of 1,500 V DC systems.

an electronic trip unit

SOC - Selected Optimized Coordination

Web tool for the selection of ABB low voltage products to be used in the following applications: Motor starting and protection, Selectivity between protection devices, Back-up protection and other devices protection, such as switch-disconnectors.

an electronic trip unit

SACE Tmax. Moulded-case circuit-breakers overview

Moulded-case circuit-breakers can be used in low voltage civil and industrial installations with 1 to 3200 A operating current.

an electronic trip unit

ATS021, ATS022. Automatic Transfer Switches

The new generation of the ATS family – ATS021 and ATS022, offers the most advanced and comprehensive power continuity solution.

Product offering

For applications in accordance to IEC 60947-2 Standard

For applications in accordance to UL 489 and CSA C22.2 Standard

For applications up to 1500V DC and 1150V AC

For variable frequency applications

Low-voltage, shockproof circuit breakers

Discover more

Applications, certifications, product software, multimedia applications, power distribution.

The most common application for moulded case circuit breakers is power distribution. SACE Tmax T4 T5, T6, T7 and T8 are available with thermomagnetic and electronic trip units to fit the needs.

TMA trip units are an option for Tmax T4, T5 and T6 up to 800A, while a wide range of electronic trip units is able to support a better customization of the protection functions:

  • PR221DS: basic trip units for standard applications on Tmax T4, T5 and T6
  • PR231/P and PR232/P: basic trip units for standard applications on Tmax T7 and T8
  • PR222DS/P: advanced trip units on Tmax T4, T5 and T6 with more options to adjust protection functions thresholds, even electronically. Ground fault protection and MODBUS network upgrade are available.
  • PR331/P and PR332/P: advanced trip units for Tmax T7 and T8. Ground fault protection and MODBUS network upgrade on PR332/P are available.

Energy metering

During the last years, the growing attention to the environmental issues together with new policies of cost reduction, which involve not only capital costs but also operational costs, has led to a wider diffusion of the energy measurements practice down to the lower distribution levels.

Aim of this tendency is to get to an optimal load management and to identify possible system inefficiencies. Examples of these loads can be machinery, any subparts of an industrial plant, the various modules that compose a data center as well as the different consumptions of a conditioning system in a mall. The possibility to measure, transmit and store data about each load is fundamental.

PR223DS is the solution for energy metering for Tmax T4, T5 and T6 in conjunction with voltage module VM210. Tmax T7 and T8 with PR332/P trip units and PR330/V are the answer for the same application for currents up to 1600A and 3200A. Mentioned trip units have an option to be integrated in a communication network.

Motor protection

Motor protection is one of the most common application for moulded case circuit breakers in low voltage installations.

Safety and reliability of solution are important aspects that must be considered when choosing and manufacturing a system for starting and monitoring motors. Start-up is a particularly critical phase for the motor itself and for the installation powering it.

When it comes to direct starting, ABB SACE proposes two different solutions:

  • a conventional system with three poles circuit breaker equipped with a magnetic only trip unit for protection against short-circuits, a thermal relay for protection against overloads and phase failure or imbalance, and a contactor to operate the motor;
  • an advanced protection system onboard the circuit breaker which integrates all the protection and monitoring functions, and a contactor for operating the motor

Tmax range offers both solutions thanks to its range of motor protection trip units.

PR221DS-I and PR231P-I trip units can be coordinated with contactors and thermal relays for the most common solutions.

Early Fault Detection and Prevention

Selectivity between protection devices in a low voltage installation is required in order to detect rapidly a fault and to isolate the fault zone so that all unaffected circuits can have service continuity.

Use of PR223EF electronic release is a way of realizing zone selectivity between Tmax T4L, T5L and T6L moulded case circuit breakers. PR223EF implements the EFDP technology (Early Fault Detection and Prevention), capable of detecting short-circuit by “predicting” the fault, based on analysis of the trend of the current derivative in relation to the time.

One of the main advantages in implementing EFDP technology and zone selectivity is the reduction in size of circuit breakers. By means of PR223EF releases, it is possible to obtain 100kA of selectivity even between two circuit breakers of the same size, so with no need to overdimension upstream device.

Certifications and Shipping Registers

SACE Tmax circuit breakers and accessories are designed, manufactured and tested in conformity with:

  • IEC 60947-2 standard;
  • EC “Low Voltage Directive” (LVD) N° 2006/95/EC
  • EC “Electromagnetic Compatibility Directive” (EMC) 2004/108/CE
  • main shipping registers such as Lloyd’s Register of Shipping, Germanischer Lloyd, Bureau Veritas, Rina, Det Norske Veritas, Russian Maritime Register of Shipping, ABS.

  ABB SACE Quality System conforms to following Standards:

  • ISO 9001 international Standard;
  • EN ISO 9001 (equivalent) European Standards;
  • UNI EN ISO 9001 (equivalent) Italian Standards;
  • IRIS International Railway Industry Standard.

ABB SACE Quality System obtained first certification with RINA certification body in 1990.

Attention to protection of the environment is a priority for ABB SACE. Confirmation of this is an Environmental Management System certified by RINA in conformity with the International ISO14001 Standard. In 1999 the Environmental Management System was integrated with the Occupational Health and Safety Management System according to the OHSAS 18001 Standard and later, in 2005, with the SA 8000 (Social Accountability 8000) Standard, committing itself to respect of business ethics and working conditions.

ISO 14001, 18001 and SA8000 recognitions together with ISO 9001 made it possible to obtain RINA Best Four Certification.

To explore the interface of ABB trip units, make a configuration, display the signals and conduct an operating simulation.

Instruction guides

Related products

Moulded Case Circuit Breakers family

Main distribution switchboards up to 6300A

Miniature Circuit Breakers family

For motor starting and power switching

Optical arc fault monitoring system

Submit your inquiry and we will contact you

Quickly find an ABB channel partner

  • Middle East and Africa
  • Asia and Oceania
  • Austria - German
  • Belgium - Dutch | French
  • Bulgaria  - Bulgarian
  • Croatia - Croatian
  • Czech Republic - Czech
  • Denmark - Danish
  • Estonia - Estonian
  • Finland - Finnish
  • France - French
  • Germany - German
  • Greece - Greek
  • Hungary - Hungarian
  • Ireland - English
  • Italy - Italian
  • Latvia - Latvian
  • Lithuania - Lithuanian
  • Luxembourg - French
  • Netherlands - Dutch
  • Norway - Norwegian
  • Poland - Polish
  • Portugal - Portuguese
  • Romania - Romanian
  • Russia - Russian
  • Serbia - Serbian
  • Slovakia - Slovakian
  • Slovenia - Slovenian
  • Spain - Spanish
  • Sweden - Swedish
  • Switzerland - French | German | Italian
  • Turkiye - Turkish
  • United Kingdom - English
  • Argentina - Spanish
  • Aruba - Spanish
  • Bolivia - Spanish
  • Brazil - Portuguese
  • Canada - English | French
  • Chile - Spanish
  • Colombia - Spanish
  • Costa Rica - Spanish
  • Dominican Republic - Spanish
  • Ecuador - Spanish
  • El Salvador - Spanish
  • Guatemala - Spanish
  • Honduras - Spanish
  • Mexico - Spanish
  • Panama - Spanish
  • Peru - Spanish
  • Puerto Rico - Spanish
  • United States of America - English
  • Uruguay - Spanish
  • Algeria - English | French
  • Angola - English | French
  • Bahrain - English | French
  • Botswana - English | French
  • Cameroon - English | French
  • Côte d'Ivoire - English | French
  • Egypt - English | French
  • Ghana - English | French
  • Israel - Hebrew
  • Jordan - English
  • Kenya - English | French
  • Kuwait - English
  • Lebanon - English
  • Madagascar - English | French
  • Mali - English | French
  • Mauritius - English | French
  • Morocco - English | French
  • Namibia - English | French
  • Nigeria - English | French
  • Oman - English
  • Pakistan - English
  • Palestine - English
  • Qatar - English
  • Saudi Arabia - English
  • Senegal - English | French
  • South Africa - English
  • Tanzania - English | French
  • Tunisia - English | French
  • Uganda - English | French
  • United Arab Emirates - English
  • Zambia - English | French
  • Zimbabwe - English | French
  • Australia - English
  • Bangladesh - English
  • China - Chinese | English
  • India - English
  • Indonesia - English
  • Japan - Japanese
  • Kazakhstan - Russian
  • Malaysia - English
  • Mongolia - Mongolian | English
  • New Zealand - English
  • Philippines - English
  • Singapore - English
  • South Korea - Korean
  • Sri Lanka - English
  • Taiwan (Chinese Taipei) - Chinese - Traditional
  • Thailand - English
  • Vietnam - English

abb.com privacy settings

Our website uses cookies which are necessary for running the website and for providing the services you request. We would also like to set the following optional cookies on your device. You can change these settings any time later by clicking "Change cookie settings" at the bottom of any page. For more information, please read our privacy notice.

We collect statistics to understand how many visitors we have, how our visitors interact with the site and how we can improve it. The collected data does not directly identify anyone.

We store choices you have made so that they are remembered across visits in order to provide you a more personalized experience.

Your browsing behavior is tracked across websites by advertising and social network service providers. You may see tailored advertising and content on other websites based on your browsing profile.

Preferences​

Advertising and tracking

Popular links

  • ABB Connect
  • ABB Electrification
  • Where to buy
  • Mission to Zero
  • ABB Ability
  • Supplying to ABB
  • Customer events
  • Investor events
  • Media events
  • Electrical and Power

Electronic trip unit

The digitrip 210+ trip unit provides easy setup for coordination and reliable protection for electrical systems in commercial, industrial, and machinery manufacturing environments..

The Digitrip 210+ trip unit provides easy setup for coordination and reliable protection for electrical systems in commercial, industrial, and machinery manufacturing environments. Designed to fit FDE-frame molded-case circuit breakers, the trip unit offers electronic trip unit functionality in an economic platform. For installation in assemblies such as panelboards and switchboards, the 210 or more electronic trip units are available in LI and LSI. Both versions include a seven-position dial to set the current rating of the breaker. The LI includes an adjustable instantaneous protection setting. The LSI includes a short delay setting with magnitude and time-delay options to improve coordination when protecting against electrical faults in a system.

www.eaton.com

This product is a Finalist in the Consulting-Specifying Engineer 2016 Product of the Year program. View more Finalists and cast your vote at www.csemag.com/votepoy (voting closes June 30, 2016).

Do you have experience and expertise with the topics mentioned in this content? You should consider contributing to our CFE Media editorial team and getting the recognition you and your company deserve. Click here to start this process.

  • Load center, electronic breakers
  • Arc flash relay
  • Arc-resistant switchgear

Related Resources

Privacy overview.

  • Car Rentals
  • Airport Transfers
  • Attractions & Tours
  • Bundle & Save
  • Destinations
  • Trip.com Rewards

Jason Isbell and the 400 Unit 2024 (Woodinville) | Chateau Ste Michelle Winery

Jason Isbell and the 400 Unit 2024 (Woodinville) | Chateau Ste Michelle Winery

Jason Isbell and the 400 Unit are set to grace the stage at the picturesque Chateau Ste Michelle Winery on July 16, 2024. Located at 14111 NE 145th Street, Woodinville, WA, 98072, this concert promises to be a night to remember. With a stellar setlist featuring hits like "Wichita Lineman," "Last of My Kind," "Cover Me Up," and more, attendees are in for a musical treat. Tickets for this highly anticipated event will be available for purchase from March 25, 2024, at 5:00 PM until July 17, 2024, at 4:00 AM. Don't miss the opportunity to experience the magic of Jason Isbell and the 400 Unit live in concert. Mark your calendars and secure your tickets early to ensure you don't miss out on this unforgettable evening of music and memories.

Provided by Chesapeake | Published Apr 11, 2024

Are you interested in Jason Isbell and the 400 Unit 2024 (Woodinville)?

More contents about woodinville.

  • Customer Support
  • Service Guarantee
  • More Service Info
  • Website Feedback
  • About Trip.com
  • Terms & Conditions
  • Privacy Statement
  • About Trip.com Group

Other Services

  • Investor Relations
  • Affiliate Program
  • List My Property
  • Become a Supplier

IMAGES

  1. The Electronic Trip Unit is a microprocessor controlled, multifunction

    an electronic trip unit

  2. LT340036 Eaton 310 LSIG Electronic Trip Unit 400A

    an electronic trip unit

  3. Electronic Trip Circuit Breaker Basics: Schneider Electric Micrologic

    an electronic trip unit

  4. The Basics Of Circuit Breaker Tripping Units

    an electronic trip unit

  5. Eaton 310-Plus Electronic Trip Units for MDL3800F Breaker Frames

    an electronic trip unit

  6. SIEMENS ETU76B ELECTRONIC TRIP UNIT

    an electronic trip unit

VIDEO

  1. Russian suburban electric multiple-unit train EP2D

  2. What's Inside the Electric Ship?

  3. ETAP Bus bar Protection

  4. Siemens ACB ETU27B Relay trip test / Siemens ETU trip test

  5. #Shorts # How Magnetic Trip Unit Tripping MCB ? # Electrical Engineering #தமிழ் #

  6. Relay Setting & Coordination II IDMT Protection for Transformer HV in ETAP II Manual Calculation

COMMENTS

  1. The Basics Of Circuit Breaker Tripping Units

    Figure 2 - TM thermal-magnetic and MA magnetic tripping units. Go back to CB tripping units ↑. Electronic tripping units // The electronic trip units instead use a microprocessor to process the current signal and operate the circuit breaker opening in case of fault.In addition to this, electronic tripping units offer more tripping criteria which are not feasible with electromechanical ...

  2. Circuit breaker electronic trip unit explained

    The Electronic Trip Unit is a microprocessor controlled, multi-function over-current protective device for application with low voltage power circuit breaker...

  3. Micrologic Trip Units

    Part of PacT Series. All Micrologic trip units provide impeccable, electronic circuit protection with adjustable protection settings for maximum system coordination and flexibility. Sophisticated functionality, such as energy and power quality metering capabilities, is integrated in the more advanced trip units.

  4. MicroLogic ™ Electronic Trip Systems

    The MicroLogic H trip unit provides additional sampling of the waveforms to measure and provide waveform capture of harmonic distortion to the 31st harmonic. MasterPact universal power circuit breakers use MicroLogic electronic trip systems to sense overcurrents and trip the circuit breaker. The MicroLogic basic trip unit is standard and all ...

  5. PDF Electronic Trip Unit for SB Encased Systems Breakers

    The Electronic Trip Unit is a microprocessor controlled multifunction overcurrent protective device for application with Siemens state-of-the art family of SB Encased Systems Breakers.The adjustment flexibility provided by the trip unit allows the user to easily accommodate load changes and other protective requirements while ...

  6. Micrologic 4 Electronic Trip Units

    The Micrologic 4 electronic trip unit is designed to protect: o Conductors in commercial and industrial electrical distribution. o Goods and people in commercial and industrial electrical distribution. On 4-pole circuit breakers, neutral protection is set on the Micrologic trip unit by using a three-position dial: o 4P 3D: neutral unprotected

  7. PDF F-frame 310+ and 210+ Electronic Trip Units

    These features are described in further detail in Section 5A. Figure 1. F-Frame 310 + Electronic Circuit Breaker. The FDE210+ electronic trip unit (Figure 2) is available in three rated frame currents (In), 100A, 150A, and 225A, for the LI protection style (catalog number suffix 21), and in two rated frame currents, 100A and 225A, for the LSI ...

  8. Section 3—Electronic Trip Systems

    ET1.0 (M-Frame only) The ET1.0 trip system is available on M-frame circuit breakers with both fixed and adjustable long-time (lr) setting and adjustable instantaneous (li) tripping. The long-time pickup is adjustable from 300 to 800 A. For fixed long-time circuit breakers, there are two circuit breaker amperage ratings.

  9. PDF Evolution of the molded case circuit breaker trip units and their ...

    thermal magnetic trip unit to the electronic trip unit which can provide a much higher degree of accuracy in sensing and responding to trip events. The illustration above (Figure 3) is a typical response of a thermal magnetic breaker in the form of a time current curve (TCC). The X axis represents current and Y axis represents time, in seconds.

  10. Characteristics of MicroLogic Electronic Trip Units

    MicroLogic electronic trip units provide the following functions: Protection of the electrical distribution or specific applications. Measurement of instantaneous values and measurement of average values (demand) for electrical quantities. Kilowatt hour metering. Operational assistance such as peak demand, customized alarms, and operation counters.

  11. Electronic Trip Circuit Breaker Basics: Schneider Electric Micrologic

    Schneider Electric Micrologic Electronic Trip units. MICROLOGIC electronic trip circuit breakers can help optimize coordination: Independent adjustments - allow one dial setting to be changed without affecting the rest of the pickup and delay levels. This allows the designer to better define the tripping characteristics needed on the system.

  12. Electronic Trip Circuit Breaker Spectra RMS

    Spectra breakers are now in the Limited life cycle phase. For circuit breakers, see SACE® Tmax® XT MCCBs. For retrofits of existing equipment, see Tmax XT Retrofit Kits for Spectra Panelboards and Switchboards. ABB & GE Industrial's Electronic Trip Circuit Breaker Mold Case Distribution. Get all the power of ABB and GE Industrial electrical ...

  13. The Basics of Molded Case Circuit Breakers

    Electronic trip units typically consist of a current transformer (CT) for each phase, a printed circuit board, and a shunt trip. The CTs monitor current and reduce it to the required ratio for direct input into the printed circuit board, the brains of the electronic trip unit. The circuit board then interprets current flow information, makes ...

  14. PDF Instruction Leaflet for the KES 310+ Electronic Trip Unit

    KES 310+ Electronic Trip Unit EATN www.eaton.com 4 Pole Trip Unit Installation Remove the 3 retaining screws from the shunt plate inserts in the base of the circuit breaker frame. Remove the conductor bar from the right-hand (fourth) pole and dis-card the conductor but keep the retaining screw.

  15. What are Thermal-magnetic or electronic trip unit?

    Thermal-magnetic trip units protect against overcurrents and short-circuits using tried and true techniques. But today, installation optimisation and energy efficiency have become decisive factors and electronic trip units offering more advanced protection functions combined with measurements are better suited to these needs. When there is an ...

  16. Evolution of the Molded Case Circuit Breaker Trip Units and their Value

    Electronic trip unit breakers are commonly referred to as 'LSI' or 'LSIG' where 'L' is the long-time trip (60-600 sec), 'S' is the short time trip (0.1 to 60 sec), and 'I' is the instantaneous trip. 'G' is the optional ground fault trip. The 'L' and 'S' functions replace the thermal element in the thermal ...

  17. Tmax T

    TMA trip units are an option for Tmax T4, T5 and T6 up to 800A, while a wide range of electronic trip units is able to support a better customization of the protection functions: PR221DS: basic trip units for standard applications on Tmax T4, T5 and T6; PR231/P and PR232/P: basic trip units for standard applications on Tmax T7 and T8 ...

  18. PDF VL Circuit Breaker Technical Information Guide

    each trip unit features adjustable settings. The interchangeable trip units are available in three (3) varieties as well: Model 525 - Thermal-magnetic Model 545 & 555 - Electronic Model 576 & 586 - Electronic with LCD display The VL family also includes Molded Case Switches, Motor Circuit Protectors, special 600V DC breakers, and other ...

  19. Electronic trip unit

    By Eaton April 14, 2016. The Digitrip 210+ trip unit provides easy setup for coordination and reliable protection for electrical systems in commercial, industrial, and machinery manufacturing environments. Designed to fit FDE-frame molded-case circuit breakers, the trip unit offers electronic trip unit functionality in an economic platform.

  20. TiSoft

    If the MCCB is equipped with electronic trip unit we can change the shape and location to bi-logarithmic chart, of its characteristic curve. This is accomplished by adjusting the following six (6) parameters as seen in the figure: I 1 = Long time pickup current → shifts left/right the left vertical segment of curve; t 1 = Long time delay → shifts up/down the negative-slope segment of curve

  21. Jason Isbell and the 400 Unit 2024 (Woodinville)

    Searching for information and tickets regarding Jason Isbell and the 400 Unit 2024 (Woodinville) | Chateau Ste Michelle Winery taking place in Woodinville on Jul 16, 2024 (UTC-8)? Trip.com has you covered. Check the dates, itineraries, and other information about Jason Isbell and the 400 Unit 2024 (Woodinville) | Chateau Ste Michelle Winery now! Trip.com has also prepared more similar exciting ...

  22. PDF Electronic Vessel Trip Reporting (eVTR) Technical Requirements Guide

    The user designs the eVTR submit request so that Sales and Catch are self-contained units of data. The separate arrays method means that you don't have to link Sales to a specific Effort. CAUTION: The total of the . kept. value ... Electronic Vessel Trip Reporting (eVTR) Technical Requirements Guide GARFO . 3/27/2024 Page . 45. of . 58 ...